Designing raised floors

Technical Specification

The lowest raised floor - EHB 18

bearing structure: TYPE I – free-standing pedestals

panel dimensions: 600 × 600 × ~17.4 mm

load class according to PN-EN 12825: 1 (2.0 kN)

permissible surface load: 10 kN/m2

deflection class according to PN-EN 12825: A (≤ 2.5 mm)

floor conductivity resistance according to PN-EN 1081: Ru [Ω] 5×104< Ru < 1×109

safety factor according to PN-EN 12825: ≥ 2

core material: gypsum-fibre

fire classification: non-flammable material

fire reaction class according to PN-EN 13501 part 1: A1

acoustics according to EN ISO 140-12 ΔLw12 dB

Office floor - EHB 30

bearing structure: TYPE I – free-standing pedestals

panel dimensions: 600 × 600 × 30 mm

load class according to PN-EN 12825: 1 (2.0 kN)

permissible surface load: 10 kN/m2

deflection class according to PN-EN 12825: A (≤ 2.5 mm)

floor conductivity resistance according to PN-EN 1081: Ru [Ω] 5×104< Ru < 1×109

safety factor according to PN-EN 12825: ≥ 2

core material: gypsum-fibre

fire classification: non-flammable material

fire reaction class according to PN-EN 13501 part 1: A1

fire resistance class according to PN-EN 13501 part 2: REI30

acoustics according to EN ISO 140-12 ΔLw: 19 dB

Server room floor - Lightweight - EHB 36 type II

upper surface of panels is covered with PVC 

bearing structure: System II – pedestals connected with steel crossbars – stringers

panel dimensions: 600 × 600 × 36 mm

load class according to PN-EN 12825: 5 (5.0 kN)

permissible surface load: 25 kN/m2

deflection class according to PN-EN 12825: A (≤ 2.5 mm)

floor conductivity resistance according to PN-EN 1081: Ru [Ω] 5×104< Ru < 1×109

safety factor according to PN-EN 12825: ≥ 2

core material: gypsum-fibre

fire classification: non-flammable material

fire reaction class according to PN-EN 13501 part 1: A1

fire resistance class according to PN-EN 13501 part 2: REI60

acoustics according to EN ISO 140-12 ΔLw: 17 dB

Server room floor - Heavy - EHB 36 Type III

upper surface of panels is covered with PVC 

bearing structure: TYPE III – screwed grate of C40/40/2mm profiles

panel dimensions: 600 × 600 × 36 mm

load class according to PN-EN 12825: 6 (6.0 kN)

permissible surface load: 30 kN/m2

deflection class according to PN-EN 12825: A (≤ 2.5 mm)

floor conductivity resistance according to PN-EN 1081: Ru [Ω] 5×104< Ru < 1×109

safety factor according to PN-EN 12825: ≥ 2

core material: gypsum-fibre

fire classification: non-flammable material

fire reaction class according to PN-EN 13501 part 1: A1

fire resistance class according to PN-EN 13501 part 2: REI60

acoustics according to EN ISO 140-12 ΔLw: 17 dB

Switchgear floor - EHB 36 Type III

upper surface of panels is covered with PVC 

bearing structure: TYPE III – screwed grate of profiles

panel dimensions: 600 × 600 × 36 mm

load class according to PN-EN 12825: 6 (6.0 kN)

permissible surface load: 30 kN/m2

deflection class according to PN-EN 12825: A (≤ 2.5 mm)

floor conductivity resistance according to PN-EN 1081: Ru [Ω] 5×104< Ru < 1×109

safety factor according to PN-EN 12825: ≥ 2

core material: gypsum-fibre

fire classification: non-flammable material

fire reaction class according to PN-EN 13501 part 1: A1

fire resistance class according to PN-EN 13501 part 2: REI60

acoustics according to EN ISO 140-12 ΔLw: 17 dB

Auditorium floor - FHB 32

bearing structure: TYPE III – screwed grade made of C 40/40/2 mm profiles or individual solution for the project

panel dimensions: 1200 × 600 × 32 mm connected with a single tongue-and-groove joint

load class according to PN-EN 13213: 6 (6.0 kN)

permissible surface load: 30 kN/m2

deflection class according to PN-EN 13213: A (≤ 2,5 mm)

floor conductivity resistance according to PN-EN 1081: Ru [Ω] 5×104< Ru < 1×109

safety factor according to PN-EN 13213: ≥ 2

core material: gypsum-fibre

fire classification: non-flammable material

fire reaction class according to PN-EN 13501 part 1: A1

fire resistance class according to PN-EN 13501 part 2: REI60

acoustics according to EN ISO 140-12 ΔLw: 16 dB

Clean Room Floor - CRF

external dimensions: 600 × 600 mm

thickness: 46 mm

structural material: steel, powder-coated

weight: approx. 15 kg.

perforation: >42%

support spacing: 600 × 600mm

support material: galvanised steel

load class in accordance with PN-EN 12825: Class 5A

point load: 5,000N

destructive force: ≥ 10,000N

safety factor: ≥ 2

construction material class load-bearing plate according to PN-EN 13501 part 1: A1 (non-flammable material)

electrostatics: (PN-EN 1081) depending on the covering used on the surface of the panels

purity class (ISO 146441-1): ISO 4

“Wet” floor for ceramic stoneware tiles

size of tiles: not more than 60 × 60 cm

load-bearing structure: TYPE I – free-standing pedestals

panel dimensions: 1200 × 600 × 32 mm, connected with a single tongue-and-groove joint

load class according to PN-EN 12825: 5 (5.0 kN)

permissible surface load: 25 kN/m2

deflection class according to PN-EN 12825: A (≤ 2.5 mm)

floor conductivity resistance according to PN-EN 1081: Ru [Ω] 5×104< Ru < 1×109

safety factor according to PN-EN 12825: ≥ 2

core material: gypsum-fibre

fire classification: non-flammable material

fire reaction class according to PN-EN 13501 part 1: A1

fire resistance class according to PN-EN 13501 part 2: REI60

acoustics according to EN ISO 140-12 ΔLw: 16 dB

Floor for large size ceramic stoneware flooring, parquet or stone

load-bearing structure: TYPE I – free-standing pedestals

panels: two layers glued together

dimensions of the first layer panel: 1200 × 600 × 32 mm, connected with a single tongue-and-groove joint

dimensions of the second layer panel: 1200 × 600 × 18 mm

load class according to PN-EN 12825: 6 (9.0 kN)

permissible surface load: 45 kN/m2

deflection class according to PN-EN 12825: A (≤ 2.5 mm)

floor conductivityresistance according to PN-EN 1081: Ru [Ω] 5×104< Ru < 1×109

safety factor according to PN-EN 12825: ≥ 2

core material: gypsum-fibre

fire classification: non-flammable material

fire reaction class according to PN-EN 13501 part 1: A1

fire resistance class according to PN-EN 13501 part 2: REI60

Acoustics according to EN ISO 140-12 ΔLw: 16 dB

TIM-EX
Privacy Overview

This website uses cookies so that we can provide you with the best user experience possible. Cookie information is stored in your browser and performs functions such as recognising you when you return to our website and helping our team to understand which sections of the website you find most interesting and useful.